Improve Burner Performance with Tigerloop® Oil De-Aerator

Tigerloop Oil De-Aerator eliminates many common oil heating problems which prevent a burner from operating at peak performance by removing air from the system, delivering foam-free fuel to the nozzle, and reducing issues caused by cold fuel — benefits which ultimately provide for cleaner, maximized combustion. Read on to learn more about this industry-leading technology which is now available from Beckett as part of our acquisition of Westwood Products.

The Advantages of Tigerloop

The Tigerloop Oil De-aerator improves the efficiency and extends the life of your oil heating systems. The Tigerloop combines the benefits of a single pipe system with a two pipe system. With a Tigerloop installed, you need only to transport oil at the nozzle firing rate (i.e. 1 gph). This allows you to use one small line from the tank to the Tigerloop, whereas with a 2 pipe installation you have to provision 2 large diameter lines that will handle oil traffic at approximately 20 gph in both directions.

Extends Filter Element Life

By filtering less oil, typically around 1 gph vs. 20 gph, you dramatically extend filter life.

Conditions Oil for Cleaner Combustion

With Tigerloop, the oil travels slowly into the house (at around 1 gph) and loops through the Tigerloop and pump multiple times, picking up heat before it is fired. Contrast this to a 2 pipe system where cold oil enters the house rapidly (20 gph) and then is immediately sent back outside into the cold tank again (this also stirs up sediment in the tank, which can clog nozzles and filters).

Eliminates Potential Leak Hazard

Without the pressurized return line that is constantly pumping oil back to the tank, Tigerloop dramatically reduces the risk of leaks.

Reduces Running Vacuum

Vacuum pulls vapor right out of the oil even in an “air tight” system. Less vacuum means less air which means clear, foam-free oil at the nozzle. Installing a Tigerloop cuts the flow rate down the firing rate of the system, typically 1 gph, dropping vacuum and improving burner efficiency while putting less strain on your oil pump and motor.

Reduces Air Up to 95%

With a 2 pipe system, all of the air and fuel in the line flows through the pump, flows by (or out) the nozzle, and then gets returned all the way back to the tank. The Tigerloop de-aerates the returning fuel before sending it back to the pump — reducing air by up to 95% and improving efficiency. The flame will sputter less, the burner will fire cleaner and prevent deposits on the heat exchanger which can build-up and interfere with the absorption of heat.

Reduce Lockouts, Flameouts, and Sputters

In a single pipe system, all air in the line has to go out the nozzle. So installing a Tigerloop will dramatically improve efficiency.

How Tigerloop Works

Having a Tigerloop is better than either a single pipe system or a 2 pipe system. Here’s how it works:

Tigerloop pulls oil through a check valve (inside the Tigerloop) and then through the pump. The pump gives the nozzle what it needs (i.e. 1 gph) and then sends the excess 19 gph back to the Tigerloop to be de-aerated. As oil rises in the Tigerloop, air escapes from the top vent until a float lifts and seals the vent. When the vent seals, the Tigerloop builds pressure (about 1/3 psi). The pressure opens a valve sending de-aerated oil back to the pump, creating the loop. If any air reaches the Tigerloop, the float drops, the vent opens, and the air is removed. The float rises again sealing the Tigerloop.

Tigerloop Products

Tigerloop®

TN

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Fuel: No. 1 & 2 Heating Oil, B5 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Tigerloop®

Ultra 

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Replacement Element: F100-10
  • Element Media: 10 micron
  • Element Canister: Epoxy Inside
  • Fuel: No. 1 & 2 Heating Oil, B5 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Beckett is the market leader in the drive towards solutions that will exceed the reduced carbon goals established by the industry in the 2019 Providence Resolution. The inclusion of B20 filters and the Tigerloop Bio Models advances Beckett’s industry leading suite of B20 rated components from tank-to-flame.

Tigerloop®

Bio

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Fuel: No. 1 & 2 Heating Oil, BioFuels up to B100 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Beckett is the market leader in the drive towards solutions that will exceed the reduced carbon goals established by the industry in the 2019 Providence Resolution. The inclusion of B20 filters and the Tigerloop Bio Models advances Beckett’s industry leading suite of B20 rated components from tank-to-flame.

Tigerloop®

Ultra B 

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Replacement Element: F100-10B
  • Element Media: 15 micron
  • Element Canister: Epoxy Inside
  • Fuel: No. 1 & 2 Heating Oil, BioFuels up to B100 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Tigerloop®

LT

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: -40˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Fuel: No. 1 & 2 Heating Oil, B5 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Features an integrated shutoff valve. It features a clear plastic bowl which houses a high efficiency sintered plastic filter element with a 50-70 micron rating.

Tigerloop®

Combi 3 

Technical Information

  • Max. Nozzle Capacity: 29.0 GPH
  • Max. Return Oil Flow: 31.7 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT (female)
  • Fuel: No. 1 & 2 Heating Oil, B5 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

The Tigerloop® Twin™ has twice the capacity for large commercial jobs (includes with commercial duty Spin-On filter)

Tigerloop®

Twin

Technical Information

  • Max. Nozzle Capacity: 52.8 GPH
  • Max. Return Oil Flow: 52.8 GPH
  • Temperature Range: 20˚ F — 105˚ F
  • Max. Inlet Pressure: 8 PSI
  • CONNECTIONS: 1/4″ – NPT
  • Spin On Filter Supplied: F100-1
  • Replacement Element: F100-11
  • Element Media: 30 micron
  • Element Canister: Epoxy Inside
  • Fuel: No. 1 & 2 Heating Oil, B5 BioHeat®

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Tigerloop®

Flexible Oil Lines 

Technical Information

  • For use as oil burner pump suction and return lines (not for nozzle line)
  • For swing-out doors and oil de-aerators
  • Steel Braided Covering
  • 24″ and 36″ Long
  • 145 PSI — 200˚ F
  • For No. 1 and 2 heating oil, BioHeat® B5 or B20

Not for use with E-diesel or any fuel containing Ethanol (alcohol)

Schedule a 1-on-1 Consultation

Want to learn more about Tigerloop and how it can make a dramatic difference in your installations? Schedule a no obligation, 1-on-1 Consultation with a Beckett Technical Specialist — we’d love to help.